On 11/03/2015, we can tell you there is a foreign body in the filter works SV3 at 114MHD.
We have yet to receive a response about this
present outdoor unit of a foreign body can damage the machine phenomenon compression history Specifically nest 01 as follows: - On 06.09.2014, the put to use - On 27.02.2015, the hot dan Slave 1 AJH108LALH sr: T200128 E94 error. Then reset, check the compressor still operating, then THD has proposed sanitation options, check filters. - On 09/03/2015, already tested in the outdoor unit filter SV3 saw filters and dirty metallic foreign bodies. - On 16.04.2015: after cleaning filter outdoor unit, indoor unit expansion valve, high pressure nitrogen blow sanitary copper tube, the signal wiring correct the conduct standards for the machine running again, but in tracking mode. - Machine works so far, it was the error, and the phenomenon of switching compressor.